Fan Heater
Features
- For use when larger heating capacities or internal forced air circulation is required.
- Designed to prevent condensation or maintain minimum temperature in enclosures.
- Thermostats are also available.
Part No. |
Watts |
Surface Temperature |
Starting Current |
Dimensions
Length x Width x Depth |
Ship Wt. lbs |
SHGL04600 |
250 |
167°F |
2.2 A |
7.00 x 3.15 x 3.15 |
2 |
SHGL04601 |
400 |
167°F |
3.5 A |
9.76 x 3.15 x 3.15 |
3 |
Operating Voltage: |
AC 110-120 V, 50/60 Hz |
Circulation Power: |
20 CFM Free Blowing |
Axial Fan: |
Ball Bearing |
Durability: |
30,000 hrs. at 68°F ambient temperature |
Heating Element: |
Resistance heating element with temperature limiter |
Heating Body: |
Extruded aluminum, black anodized |
Connection: |
3 pole terminal for 12 AWG |
Mounting: |
Easily installed by clip mounting on 35 mm DIN rails (included) |
Protection Class: |
1 (tested for grounding at 1250 V) |
Protection: |
IP20 |
Approval: |
UL Recognized Component, cUL Recognized Component, CE |